Infrared roof inspection
Thermal imaging roof inspections locate suspected wet insulation on flat and low-slope roofs when weather and timing are suitable.
Infrared thermography shows differences in surface temperature. We use thermal imaging from the roof, the ground and the air to screen roofs and building envelopes for suspected moisture, missing insulation and air leakage, then verify what matters before it reaches your report.


Drag to compare. Illustration of a thermal view; actual thermal images show measured surface temperatures.
Wet materials, missing insulation and air leaks change how a surface heats and cools. An infrared camera turns those differences into an image, which makes it an efficient way to screen large roofs and building walls.
A thermal image is not proof on its own. Sun, reflections, surface materials and recent weather can all create patterns that look like a problem. We interpret each anomaly against the building’s construction and conditions, then verify the ones that matter.
Thermal imaging roof inspections locate suspected wet insulation on flat and low-slope roofs when weather and timing are suitable.
Large commercial and industrial roofs surveyed efficiently, with suspect areas marked for verification.
Infrared moisture detection in roofs, walls and ceilings, confirmed with meters or probes.
Walls, windows and transitions scanned for suspected moisture, insulation gaps and air leakage.
Infrared building inspection of offices, retail and multifamily buildings to support maintenance and capital planning.
Drone thermal imaging for roofs and elevations that are difficult or unsafe to reach.
We schedule every infrared inspection around the conditions it needs, which is why some roof surveys happen in the evening.
Surface water and dew hide what is underneath.
Wind cools the surface and washes out differences.
Sun loads the roof so wet areas hold heat after sunset.
Wall scans need a real difference between inside and outside.
Screening vs. confirmed. Infrared identifies suspected conditions. We report moisture or damage as confirmed only after verification, such as moisture readings, core samples or selective openings where authorized.
Confirm goals, access and the right weather window.
Drone or handheld thermography of the roof or envelope.
Review anomalies against construction and conditions.
Confirm suspect areas with readings or cores where authorized.
Annotated thermal images, maps and recommendations.
Our infrared work is informed by ASTM C1153, ASTM E3216 and ASTM C1060. Drone operations follow FAA requirements, including 14 CFR Part 107. See Industry Standards.
Summit Building Group: CSLB #1122392 · IICRC Certified Firm · Angelo Pacheco, HCI-C, IICRC BMI and WRT.
It can locate suspected wet insulation under a roof membrane by showing areas that hold heat longer after sunset. Suspect areas are then verified before they are reported as wet.
No. Infrared cameras detect surface temperature differences. Moisture is one cause of those differences, so readings are interpreted and verified.
Wet insulation absorbs and holds more heat than dry insulation. After sunset, wet areas stay warmer and show up more clearly on a dry roof.
Yes, for large roofs and upper elevations. Drone operations follow FAA requirements, including 14 CFR Part 107.